• Products
  • Solutions
  • Support
  • Contact
  • Order OnlineOrder Online
Mouseover to zoom-in
AXM-NET2 product images.
Right quarter-angle view of the AXM-NET2 with the Acuvim II
Right quarter-angle view of the AXM-NET2 with the Acuvim II
Left quarter-angle view of the AXM-NET2
Right quarter-angle view of the AXM-NET2

MODBUS DUAL ETHERNET METER MODULE

The AXM-NET2 is an entry-level dual Ethernet communication module for Acuvim II and Acuvim L Series power meters. The module supports Modbus TCP/IP communication, enabling remote access to measured data for industrial energy monitoring and power management applications. Encrypted HTTPS connectivity provides a built-in Web Interface for real-time meter monitoring and automatic data uploads to AcuCloud.

  • Modbus TCP/IP communication over dual Ethernet ports.
  • Dual Ethernet ports support daisy-chain topology, eliminating the need for external switches.
  • SNTP time synchronization with configurable time-zone support for accurate timestamping.
  • Built-in Web Interface for remote real-time data monitoring and system management.
  • Remote configuration and maintenance via the built-in Web Interface.
  • Supports secure data post to AcuCloud via encrypted HTTPS.
  • Automatic local buffering and retransmission ensure parameter updates to AcuCloud during network interruptions.

AXM-NET2 Overview

Cost-Effective Modbus TCP/IP Ethernet Module

The AXM-NET2 enables Modbus TCP/IP communication for Acuvim II and Acuvim L Series power and energy meters, allowing real-time meter data to be accessed remotely and integrated with gateways and energy management systems over Ethernet networks. For applications requiring additional communication protocols, onboard data logging, or enhanced functionality, the advanced AXM-WEB2 module provides expanded capabilities.

Dual Ethernet Ports

The AXM-NET2 includes dual 10/100 Mbps Ethernet ports supporting daisy-chain topology to connect multiple meters without external switches, simplifying network architecture and reducing installation complexity.

Acuvim II and AXM-NET2 front quarter angle view

Communication Modules

Acuvim II
Acuvim L
AXM-NET2
AXM-WEB2 FOLC
AXM-WEB2
AXM-WEB2-D
Interface
Ethernet RJ45 Port 2 1 2 2
Fiber Optics LC
Wi-Fi
Data Logging
Local Memory 8MB 8GB 8GB 8GB
Ethernet Protocol Support
Modbus TCP/IP
BACnet IP
IEC 61850 2nd Edition
DNP 3.0 V2 Over IP
EtherNet/IP
IPv6
MQTT
Networking Protocols Supported
Time Synchronization SNTP NTP NTP NTP
RSTP
SNMP V3
Serial Protocol
Modbus RTU
Data Post
HTTPS Push
FTP Post
Web Server
HTTPS Webserver
Acuvim II
Acuvim L
Local Memory 8MB
Modbus RTU
AXM-NET2
Ethernet RJ45 Port 2
Modbus TCP/IP
Time Synchronization SNTP
RSTP
HTTPS Push
HTTPS Webserver
AXM-WEB2 FOLC
Ethernet RJ45 Port 1
Fiber Optics LC
Wi-Fi
Local Memory 8GB
Modbus TCP/IP
BACnet IP
IEC 61850 2nd Edition
DNP 3.0 V2 Over IP
EtherNet/IP
IPv6
MQTT
Time Synchronization NTP
RSTP
SNMP V3
HTTPS Push
FTP Post
HTTPS Webserver
AXM WEB2
Ethernet RJ45 Port 2
Wi-Fi
Local Memory 8GB
Modbus TCP/IP
BACnet IP
IEC 61850 2nd Edition
DNP 3.0 V2 Over IP
EtherNet/IP
IPv6
MQTT
Time Synchronization NTP
RSTP
SNMP V3
HTTPS Push
FTP Post
HTTPS Webserver
AXM WEB2-D
Ethernet RJ45 Port 2
Local Memory 8GB
Modbus TCP/IP
BACnet IP
IEC 61850 2nd Edition
DNP 3.0 V2 Over IP
EtherNet/IP
IPv6
MQTT
Time Synchronization NTP
RSTP
SNMP V3
HTTPS Push
FTP Post
HTTPS Webserver

AXM-NET2 Features

Encrypted HTTPS communication feature of the AXM-NET2
Encrypted HTTPS Communication

The AXM-NET2 uses HTTPS communication with TLS 1.2 encryption to provide secure access to the built-in Web Interface for real-time meter monitoring, network configuration, and system management, as well as encrypted connection to AcuCloud.

Reliable data upload feature of the AXM-NET2
Reliable Data Post

Metering parameters are automatically updated through data posts to AcuCloud, with automatic local buffering and retransmission to ensure data continuity during network interruptions.

Remote device configuration feature of the AXM-NET2
Remote Device Configuration

The AXM-NET2 enables remote configuration and maintenance of the connected meter through a built-in Web Interface, allowing factory reset and reboot functions without requiring local access.

SNTP time synchronization feature of the AXM-NET2
SNTP Time Synchronization

The AXM-NET2 supports SNTP time synchronization with configurable time-zone settings (UTC ±14:00), ensuring accurate timestamping of uploaded and displayed data.

Built-in NET2 Web Interface

NET2 Web Interface - Network Configuration
NET2 Web Interface - Power & Energy
NET2 Web Interface - Basic Metering
NET2 Web Interface - Device Settings

Stay Connected to Energy Data

Remote Data Access
Remote Data Access

The AXM-NET2 provides remote access to real-time measurement data through its built-in Web Interface, with tabular reports for basic metering, power & energy, and phase angle. Dedicated webpages update every 10 seconds for continuous monitoring and analysis.

Basic Metering
Basic Metering

Monitor basic metering data for each phase, including voltage, current, power, power factor, and frequency. A fast data refresh rate allows quick verification of system conditions, wiring, and load status.

Power & Energy
Power & Energy

Access power & energy data, including energy consumption and generation for import and export, per-phase energy breakdown, and power demand for each phase.

Phase Angle
Phase Angle

Analyze the phase angles of voltage and current to determine the polarity of the connected current transformer.

AXM-NET2 Product Map

AXM-NET2 Product Map
1

Dual Ethernet Ports

Supports Modbus TCP/IP and daisy-chain topology

3

Acuvim II Series

Compatible with any Acuvim II/L meters

2

Remote Access

View metering data remotely via a Web Interface

4

Data Encryption

Encrypted data post to AcuCloud

1

Dual Ethernet Ports

Supports Modbus TCP/IP and daisy-chain topology

2

Remote Access

View metering data remotely via a Web Interface

3

Acuvim II Series

Compatible with any Acuvim II/L meters

4

Data Encryption

Encrypted data post to AcuCloud

AXM-NET2 FAQ

What is the difference between AXM-NET2 and AXM-WEB2?

The AXM-NET2 is an entry-level Ethernet-based communication module that forms part of the AXM-WEB2 product line, offering Modbus TCP/IP communication and an encrypted HTTPS Web Interface for real-time monitoring and data post to AcuCloud.

Are the two Ethernet ports on the AXM-NET2 independent?

No. The two RJ45 ports are internally bridged and share a single logical IP address and network configuration. They are designed for a daisy-chain topology and operate within the same broadcast domain.

Is Rapid Spanning Tree Protocol (RSTP) supported on the AXM-NET2?

Yes. RSTP is enabled by default and cannot be disabled, which prevents network loops and ensures fast recovery in redundant topologies.

Does the AXM-NET2 store historical data locally?

No. The AXM-NET2 does not provide local historical log exports through the Web Interface, and historical data must be accessed through AcuCloud or the Acuview 2 Meter Data Management Software.

Does the AXM-NET2 support firmware upgrades?

No. Firmware upgrades must be performed using Acuview 2 software over Modbus TCP/IP for both the module firmware and the meter firmware.