The values in the Modbus Registers of the Acuvim II series power meter may not represent the values that are seen from the display of the meter.
To convert the raw data read from the Modbus registers a relationship must be applied to the raw values.
The relationship between the raw values in the registers and the parameters can be seen below:
Note: For meters with RCT, 333mV and mA current input take CT2 as 1.
In order not to manually perform these calculations or program these relationships, the 'Real-Time Reading' setting on the meter (S28 Para Mode) needs to be configured to 'Primary' so that the values in the Modbus registers is the same value without any scaling required.